KPM31D Socket type outdoor single phase electricity ANSI meter

KPM31D Socket type outdoor single phase electricity ANSI meter

KPM31D Socket type outdoor single phase electricity ANSI meter

KPM31D Socket type outdoor single phase electricity ANSI meter is in full compliance with the international standard ANSI_C12.21-2006 on the 0.5S class energy meter of the relevant technical requirements. It integrates measurement of voltage, current, power, demand power consumption and  communication together.

Features

  • Socket type, Outdoor
  • Complied with C12.1 C12.10 C12.18 C12.19 C12.20
  • LCD 6+1 Energy display way, Display instantaneous item: Voltage, Current, Active Power.
  • Communication port: optical port, RS485, RF, and PLCLORA Optional
  • Max 4 rates can be set, default T1
  • Max Demand display
  • 2 levels of password
  • 12 months History metering data and 50 events of power on/off and meter reset
  • Dis-connect Relay optional
  • Rated 100A 200A for option
  • FM1S FM2S optional

Single Phase Multi-Tariff ANSI Meter(FM2S)
 
MODEL FM2S CL200 3W FM2S CL100 3W FM2S CL200 3W FM2S CL100 3W
Power Supply type Transformer Transformer Transformer Transformer
Current Measurement Type Current Transformer Current Transformer Current Transformer Current Transformer
Dis-Connect Relay  × ×
Optical Port
RS485 Port        
RF Port        
PLC Port        
Lora Port        
ILAC or  KEMA

Single Phase Multi-Tariff ANSI Meter(FM1S)
 
MODEL FM1S L200  2W  FM1S L100  2W FM1S L200  2W  FM1S L100  2W FM1S L200 2W FM1S L100 2W
Power Supply type Transformer Transformer Transformer Transformer Transformer Transformer
Current Measurement Type Current Transformer Current Transformer Current Transformer Current Transformer Shunt  Shunt 
Dis-Connect Relay  × × ×
Optical Port
RS485 Port         □  □ 
RF Port         □  □ 
PLC Port         □  □ 
Lora Port         □  □ 
ILAC or  KEMA
Voltage Operating Voltage 80%~120%Un    (Un=240V)
Current Test Current(TA) CL200: 30A
CL100: 15A
Current range that guarantees accuracy CL200: 0.6~200A  (2%TA~Imax)
CL100: 0.3~100A  (2%TA~Imax)
Starting Current CL200: 0.030A     (30mA)
CL100: 0.015A     (15mA)
Other parameters Frequency 60Hz±5%
Kh 10
Kt 1
Power supply type Transformer type
Current sampling mode  Current transformer
Power Consumption Voltage circuit: <1W, 5VA
Current circuit: <0.25VA/Each
Test  Immunity to impulse voltage Surge >8kV(1.2/50US)
Confidence Insulation strength 4kV,60Hz for 1 min
  Relative humidity 0%~95% no condensation
Temperature Operating Temperature – 40°C ~ + 80°C
Storage and Transportation – 45°C ~ + 85°C
Temperature
LCD Operating Temperature – 40°C ~ + 85°C
Clock accuracy < 0.5 s/d, at 23°C
Battery Li-SOCI2, 3.6V,1200mAh for clock and LCD display during power off.
Communication Port  Optical port  ANSI type 2 with 9600bps
RS485 port  Optional
RF   port  Optional
PLC  port Optional
Lora port Optional
Demand Maxim demand  Maxim demand ;date; time;
Dis-connect Relay 15(100)A    Optional
30(200)A

KPM31D Socket type outdoor single phase electricity ANSI meter Single phase 3 wire wiring diagram

Single phase 2 wire wiring diagram